Installation Manual

25
Lutron integration protocol
PROGRAMING Command Formats
PROGRAMMING Command-specific fields
Action Numbers and Parameters:
Description Action Number Parameters
Get (?) display programming of a specific phantom
button
1
None None
Get (?) display Stop-If-Moving configuration of a
specific phantom button
2
4 None
Example PROGRAMMING Commands
The following examples show how to verify the programming of the phantom buttons of a
QSE-CI-NWK-E with an Integration ID of “1.”
Operation Command String
Display programming of phantom button 1 ?PROGRAMMING,1,1<CR><LF>
Display programming of all phantom buttons ?PROGRAMMING,1<CR><LF>
Display Stop-If-Moving configuration of phantom button 5 ?PROGRAMMING,1,5,4<CR><LF>
Display Stop-If-Moving configuration of all phantom buttons ?PROGRAMMING,1,0,4<CR><LF>
NOTES
1. To display programming of all phantom buttons, leave the button number field blank.
2. To display Stop-If-Moving configuration of all phantom buttons, use button number 0.
Operation
Command
?PROGRAMMING, 1, Button Number, Action Number
Integration ID or Serial # of
the QSE-CI-NWK being used
Use “PROGRAMMING Command-specific fields” tables
to complete these command fields.
Phantom Button Number
(can be 1100)
QS Standalone (continued)
System Commands (continued)
PROGRAMMING Commands (continued)
Continued on next page…