Lutron integration protocol
MONITORING Command Formats
MONITORING Command-specific fields
Monitoring Type:
Description Monitoring Type
Set (#) or Get (?) Diagnostic Monitoring 1
Set (#) or Get (?) Button Monitoring (if enabled, button actions will be reported) 3
Set (#) or Get (?) LED Monitoring (if enabled, LED states will be reported) 4
Set (#) or Get (?) Zone Monitoring (if enabled, zone levels will be reported, i.e. dimmer,
shade, contact closure output level)
5
Set (#) or Get (?) Reply State (if disabled, all messages FROM the integration access
point will cease)
11
Set (#) or Get (?) Prompt State (if disabled, the prompt will not be printed to the terminal) 12
Set (#) or Get (?) State of All Monitoring (except Reply and Prompt) 255
Action Numbers:
Action Action Number
Enable 1
Disable 2
Example MONITORING Commands
Operation Command String
Execute: #MONITORING, Monitoring Type, Action Number
Disable Diagnostic Monitoring. #MONITORING,1,2<CR><LF>
Enable Event Monitoring. #MONITORING,2,1<CR><LF>
Query: ?MONITORING, Monitoring Type
Is Diagnostic Monitoring disabled? ?MONITORING,1<CR><LF>
Response: ~MONITORING, Monitoring Type, Action Number
Diagnostic Monitoring is disabled. ~MONITORING,1,2<CR><LF>
Setup
Wired
RF
Communication
Repeater Status
1
3
4
2
M
Main Repeater
Power
Repeater Link
COM
9 V
1
N / C
MUX
MUX
2
3
4
AddTest
Integrate
Program / Integrate
RS232
Ethernet
USB
RadioRA 2 (continued)
System Commands (continued)
MONITORING Commands
Use “MONITORING Command-specific fields”
tables to complete these command fields.
Operation
Command
#MONITORING, Monitoring Type, Action Number