Lutron integration protocol
Quantum (continued)
Integration Access Points (continued)
Connection Information
Provides an RS232 and Ethernet connection to communicate with external equipment.
RS232
The RS232 connection has the following communication settings:
• Baud Rate 9600/19200/38400/115200 (set via dipswitch on unit)
• 8 data bits
• No parity bit
• 1 stop bit
• No flow control
Ethernet
Configuring the control interface to communicate over a network takes not only knowledge of
the Quantum system, but of networking as well. Installers with limited networking knowledge are
advised to contact a networking professional before attempting to connect a QSE-CI-NWK-E
through a network. The information below will help an installer communicate the QSE-CI-NWK-E
configurations to a network professional.
The installer will make any necessary changes to the control interface using the Lutron DeviceIP or
Quantum PC software tool and the network professional can make any necessary changes to the
networking equipment.
Single Ethernet Port
• IEEE® 802.3 Auto-Sensing 10BaseT / 100BaseTX
• Supports MDI/MDIX auto-crossover (no crossover cable needed).
• Female 8P8C “Computer RJ-45” socket
• Green “Connect” LED, Amber “Activity” LED
• Use Cat 5 cabling or better
TCP / IP Settings
• IP Address: <static default = 192.168.250.1>
• Subnet Mask: <static default = 255.255.255.0>
• Gateway: <static default = 0.0.0.0>
Protocols Used for Integration
• TELNET
Telnet Server
• Used by third party equipment (e.g., touch screen)
• Limited to transferring ASCII characters
• Telnet Port number is 23
• Login #1: nwk
•
Login #2: nwk2