Installation Manual
42
Lutron integration protocol
SHADEGRP Command Formats
SHADEGRP Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) Shade Group Level 1
Level
1
= 0 –100 or 0.00 –100.00
Delay
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Set (#) Start Raising
4
2 None
Set (#) Start Lowering
4
3 None
Set (#) Stop Raising or
Lowering
4 None
Set (#) or Get (?) Current
Preset
6
Preset Number
5
= 0 –30
NOTES
1. The Level is accepted as a percentage, where 100% is fully open and 0% is fully closed.
2. The Delay time is optional. When not used, the system will use a zero-second delay. The minimum delay time is
0seconds. The maximum delay time is 4 hours.
3. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a delay time is specified
as 1.45 seconds a value of 1.25 seconds will be used.
4. When a Raise / Lower command is issued, the shade group’s level will continue to go towards open / close until a Stop
command is received.
5. Preset 0 is the Open Preset and Preset 30 is the Closed Preset.
Example SHADEGRP Messages
Operation Command String
Execute: #SHADEGRP, Integration ID, Action Number, Parameters
Set shade group to 70% (Delay = 2 sec) #SHADEGRP,2,1,70,2<CR><LF>
Lower shade group. #SHADEGRP,2,3<CR><LF>
Query: ?SHADEGRP, Integration ID, Action Number
What is the current active preset? ?SHADEGRP,2,6<CR><LF>
Response: ~SHADEGRP, Integration ID, Action Number, Parameters
Shade group Preset 2 is currently active. ~SHADEGRP,2,6,2<CR><LF>
Quantum (continued)
System Commands (continued)
SHADEGRP Commands
Use “SHADEGRP Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#SHADEGRP
1
, 2, Action Number, Parameters
NOTE
1. SHADEGRP can be used to control only those shade groups of a Quantum system that have been assigned to a
particular integration access point. Please refer to the Q-Design software (Integration Tab) or Quantum Integration Report
for details of what shade groups are available for control and monitoring.
Continued on next page…