Installation Manual
50
Lutron integration protocol
OUTPUT Command Format
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) or Get (?) Output Level 1
Level
1
= 0 –100 or 0.00 –100.00
Fade
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Delay
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Set (#) Start Raising
4
2 None
Set (#) Start Lowering
4
3 None
Set (#) Stop Raising or Lowering
4
4 None
Set (#) or Get (?) Flash Frequency 5
Fade
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Delay
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Set (#) Pulse Time 6
Pulse
5
time in: SS.ss
3
, SS, MM:SS, or HH:MM:SS,
or Delay
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Set (#) Tilt Level 9
Tilt level in % = 0.00–100
6
Fade
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Delay
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Set (#) Lift and Tilt Levels 10
Lift
1
= 0 –100 or 0.00 –100.00
Tilt
1
= 0 –100
6
or 0.00–100.00
6
Fade
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Delay
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Set (#) Start Raising Tilt 11 None
Set (#) Start Lowering Tilt 12 None
Set (#) Stop Raising or Lowering Tilt 13 None
Set (#) Start Raising Lift 14 None
Set (#) Start Lowering Lift 15 None
Set (#) Stop Raising or Lowering Lift 16 None
Get (?) Horizontal Sheer Shade Region 28
Regions: 0 = Lift, 1 = Tilt
NOTES
1. The Level/Lift/Tilt is taken as a percentage.
2. The Fade and Delay time are optional. When not used, the system will use a one-second fade time with zero-second
delay. The minimum fade and delay time is 0 seconds. The maximum fade and delay time is 4 hours. For shade outputs,
the Fade parameter has no effect (since shades have fixed speeds) but it is required when specifying an optional delay.
3. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a fade time is specified
as 1.45 seconds a value of 1.25 seconds will be used.
4. When a Raise / Lower command is issued, the output’s level will continue to go towards high end / low end until a Stop
command is received.
5. The default time is one second.
6. 50 for Horizontal Sheer Blinds.
HomeWorks QS (continued)
System Commands
OUTPUT Commands
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#OUTPUT
1
, 2, Action Number, Parameters
NOTE
1. OUTPUT commands can be used to control system lighting zones, individual shades, and contact closed outputs.
Continued on next page…