Installation Manual

70
Lutron integration protocol
myRoom plus (continued)
System Commands (continued)
AREA Commands
AREA Command Formats
AREA Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Get (?) Occupancy State
1
8 3 = Occupied
4 = Unoccupied
Use “AREA Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
?AREA
1
, 2, Action Number, Parameters
Continued on next page…
Assembled in U.S.A.
50015757 Rev. A
GCU-HOSP
Guestroom Control Unit
+ 44.(0)20.7680.4481
+ 1.800.523.9466
lutron.com
243C IND. CONT. EQ.
IEC PELV/NEC Class 2
®
NOTE
1. This is not for Guest Presence Detection of the room.
NOTE
1. AREA commands cannot be sent to areas that contain other areas, such as a room that has multiple areas within it
(e.g., bedroom, bathroom).
Example AREA Messages
Operation Command String
Execute: #AREA, Integration ID, Action Number, Parameters
Set area level to 75% (Fade = 4 sec, Delay = 2 sec) #AREA,2,1,70,4,2<CR><LF>
Lower Area. #AREA,2,3<CR><LF>
Query: ?AREA, Integration ID, Action Number
Is the area occupied? ?AREA,2,8<CR><LF>
What is the current active scene? ?AREA,2,6<CR><LF>
Response: ~AREA, Integration ID, Action Number, Parameters
The area is currently occupied. ~AREA,2,8,3<CR><LF>
Area Scene 2 is currently active. ~AREA,2,6,2<CR><LF>