Installation Manual
76
Lutron integration protocol
DEVICE Command-specific fields (continued)
Component Numbers (continued):
Component Component Number Available Actions
Shade Column 1 Open LED
1
174 Get (?) LED state
Shade Column 1 Preset 1 LED
1
175 Get (?) LED state
Shade Column 1 Close LED
1
211 Get (?) LED state
Shade Column 2 Open LED
1
183 Get (?) LED state
Shade Column 2 Preset 1 LED
1
184 Get (?) LED state
Shade Column 2 Close LED
1
220 Get (?) LED state
Shade Column 3 Open LED
1
192 Get (?) LED state
Shade Column 3 Preset 1 LED
1
193 Get (?) LED state
Shade Column 3 Close LED
1
229 Get (?) LED state
NOTE
1. Not supported in QS Standalone.
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) Press or Occupied 3 None
Set (#) Release or Unoccupied 4 None
Set (#) Current Scene
1,2
7 Scene
Set (#) or Get (?) LED State
3
9 0 = Off
1 = On
2 = Normal-Flash: 1 flash every second
2
3 = Rapid-Flash: 10 flashes every second
2
Set (#) Scene Save 12 Scene
Set (#) or Get (?) Light Level
4,5
14 Level = 0 –100 or 0.00 –100.00
Fade
6
in: SS.ss
7
, SS, MM:SS, or HH:MM:SSJ79 (QS
Standalone fade: maximum 4 hours)
Delay
6
in: SS.ss
7
, SS, MM:SS, or HH:MM:SS (QS Standalone
delay: maximum 4 hours)
Set (#) Zone Lock
8
15 0 = Off; 1 = On
Set (#) Scene Lock
8
16 0 = Off; 1 = On
Set (#) Sequence State
8
17 0 = Off
1 = Sequence through Scenes 1–4
2 = Sequence through Scenes 5–16
Set (#) Start Raising
4,5
18 None
Set (#) Start Lowering
4,5
19 None
Set (#) Stop Raising or Lowering
4,5
20 None
Set (#) or Get (?) Timeclock State 34
0 = Disabled
1 = Enabled
NOTES
The number of zone controllers available matches the number of zones a particular model supports.
1. Not supported in HomeWorks QS / myRoom plus.
2. Not supported in RadioRA 2.
3. Quantum or HomeWorks only. “Set” is for unprogrammed buttons and buttons with LED logic ‘Defined by Integration.’
4. Use OUTPUT command with equivalent command in RadioRA 2.
5. Use OUTPUT command with equivalent command in HomeWorks QS / myRoom plus.
6. The Fade and Delay time are optional. When not used, the system will use a one-second fade time with zero-second delay.
7. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a fade time is specified
as 1.31 seconds a value of 1.25 seconds will be used.
8. QS Standalone only.
GRAFIK Eye QS (continued)
DEVICE Commands (continued)
1 2 3 4 5 6
Scene 1
OK
Fade Time
03 Seconds
Continued on next page…