Operation
Command
Integration ID (example)
#DEVICE, 5, Component Number, Action Number, Parameters
DEVICE Command-specific fields
Component Numbers:
Component Component Number Available Actions
Occupancy Sensors 1 – 4 136 – 139 Report (~) Occupied, Report (~) Unoccupied
Loop 1 Ballast Occupancy Sensors
140 – 203 Report (~) Occupied, Report (~) Unoccupied
Loop 2 Ballast Occupancy Sensors
204 – 267 Report (~) Occupied, Report (~) Unoccupied
Zone 1–Zone 100
1, 2, 3
1001–1100 Set or Get Light Level, Raise, Lower, Stop
Area 1–Area 100
1, 3
1201–1300 Set or Get Scene, Set Light Level, Raise, Lower, Stop
NOTES
1. Zones and areas are created and configured using the Lutron ESN Configuration Tool on an iPhone or iPod Touch mobile
device, the Quantum Q-Design Tool, the HomeWorks QS Lutron Designer, or the myRoom Lutron Designer. Only those
areas and zones that have been configured using one of these tools are accessible through integration.
2. Assigned zones can be given an individual Integration ID and controlled using the #OUTPUT command. For more details
on setting the output Integration ID of a zone component, see the Integration Access Point section of the system that
contains the ESN.
3. When the ESN is part of a Quantum, HomeWorks QS or myRoom plus system, the #AREA and #OUTPUT commands
found in the Quantum “System Commands” section of this integration document should be used.
Action Numbers and Parameters:
Action Action Number Parameters
Report (~) Occupied 3 None
Report (~) Unoccupied 4 None
Set (#) or Get (?) Current Scene 7 Scene
Set (#) Scene Save
1
12 Scene
Set (#) or Get (?) Light Level 14
Level = 0 –100 or 0.00 –100.00
Fade
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Delay
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Set (#) Scene Lock
4
16 0 = Off; 1 = On
Set (#) Sequence State
4
17 0 = Off; 1 = Sequence through Scenes 1– 4;
2 = Sequence through Scenes 5–16
Set (#) Start Raising 18 None
Set (#) Start Lowering 19 None
Set (#) Stop
Raising or Lowering
20 None
NOTES
1. Available only with Energi Savr Node Firmware > 6.x.
2. The Fade and Delay time are optional. When not used, the system will use a one-second fade time with zero-second delay.
3. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a fade time is specified
as 1.31 seconds, a value of 1.25 seconds will be used.
4. QS Standalone only.
NOTE
1. Not Supported in HomeWorks QS / myRoom plus.