Installation Manual
5
Lutron integration protocol
DEVICE Command-specific fields
Component Numbers:
Refer to device specific tables for lists of Component Numbers.
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) Enable
1
1 None
Set (#) Disable
1
2 None
Set (#) Press, Close, or Occupied 3 None
Set (#) Release, Open, or Unoccupied 4 None
Set (#) Hold
2
5 None
Set (#) Multi-tap
2
6 None
Set (#) or Get (?) Current Scene
1,2
7 Scene
Set (#) or Get (?) LED State 9
0 = Off
1 = On
2 = Normal Flash
2
3 = Rapid Flash
2
Set (#) or Get (?) Light Level
3
14 0–100 or 0.00–100.00
SS.ss, SS, MM:SS, or HH:MM:SS
SS.ss, SS, MM:SS, or HH:MM:SS
NOTES
1. Quantum 2.7 and higher.
2. Not supported in RadioRA 2.
3. Not supported by Quantum.
DEVICE Command Formats
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE, 5, Component Number, Action Number, Parameters
Continued on next page…
Integrator’s Reference (continued)
DEVICE: Command Summary
Device integration commands allow the user to access components of the system such as a
physical device. The user can activate programming via button presses, releases, etc., as well as
monitor those same events as they occur in the system.