Installation Manual
88
Lutron integration protocol
DEVICE Command-specific fields
Component Numbers:
Component Component Number Available Actions
Zone 1 – Zone 4
1,2
1 – 4 Set or Get Light Level, Raise, Lower, Stop
NOTES
1. Assigned zones can be given an individual Integration ID and controlled using the #OUTPUT command. For more details
on setting the output Integration ID of a zone component, see the Integration Access Point section of the system that
contains the QS Motor Module.
2. When the QS Motor Module is part of a Quantum system, then the commands found in the Quantum “System
Commands” section of this integration document should be used.
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) Light Level 14
Level = 0 –100 or 0.00 –100.00
1
Fade
2
in: Always use 0
Delay
3
in: SS.ss
4
, SS, MM:SS, or HH:MM:SS
Set (#) Start Raising 18 None
Set (#) Start Lowering 19 None
Set (#) Stop Raising or Lowering 20 None
NOTES
1. Setting the level to 0% will cause the output to travel in the Closed direction; setting the level to 100% will cause the
output to travel in the Open direction; setting any level from 1 – 99% will be ignored by the output. Querying its level will
report 0 or 100%, based on the last direction it moved.
2. Fade is not available for Motor Loads because they move at a constant rate. The parameter must be entered, but is
ignored.
3. The delay time is optional. When not used, the system will use a zero-second delay.
4. Fractional seconds “SS.ss” will be rounded down to the nearest quarter-second. For example, if a fade time is specified
as 1.31 seconds, a value of 1.25 seconds will be used.
DEVICE Command Format
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE, 5, Component Number, Action Number, Parameters
Energi Savr Node QS
for Motor Module (International)
HomeWorks QS / myRoom Power Module
for Motor Module (continued)
DEVICE Commands
Continued on next page…