Installation Manual
91
Lutron integration protocol
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) or Get (?) Zone Level 1 0–100 or
0.00–100.00
SS.ss
1
, SS, MM:SS, or HH:MM:SS
Set (#) Start Raising 2 None
Set (#) Stop Lowering 3 None
Set (#) Stop
Raising or
Lowering
4 None
Set (#) Flashing
2
5 SS.ss
1
, SS, MM:SS, or HH:MM:SS
Set (#) Pulse Time 6
SS.ss
1
, SS, MM:SS, or HH:MM:SS
Set (#) Motor Jog Raise 18 None
Set (#) Motor Jog Lower 19 None
Set (#) Motor 4-Stage Jog
Raise
20 None
Set (#) Motor 4-Stage Jog
Lower
21 None
NOTES
1. Fractions are rounded up to the closest ¼ second.
2. To stop a dimmer from flashing, send it to a valid level (action 1).
OUTPUT Command Format
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#OUTPUT, 6, Action Number, Parameters
Remote Power Module (continued)
OUTPUT Commands