Installation Manual
93
Lutron integration protocol
Low-Capacity Switching/Phase-Adaptive
DIN Power Module (1A/output) (continued)
DEVICE Commands
1
DEVICE Command Formats
iPhone and iPod Touch are trademarks of Apple, Inc., registered in the U.S. and other countries.
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE, 5, Component Number, Action Number, Parameters
DEVICE Command-specific fields
Component Numbers:
Component Component Number Available Actions
Zone 1 – Zone 4
1, 2, 3
5 – 8 Set or Get Light Level, Raise, Lower, Stop
Area 1 – Area 4
2, 3
10 –13 Set or Get Scene, Set Light Level, Raise, Lower, Stop
Contact Closure Input
26 Report Open, Report Closed
NOTES
1. Zones and areas are created and configured using the HomeWorks QS Lutron Designer, or the myRoom Lutron
Designer. Only those areas and zones that have been configured using one of these tools are accessible through
integration.
2. Assigned zones can be given an individual Integration ID and controlled using the #OUTPUT command. For more details
on setting the output Integration ID of a zone component, see the Integration Access Point section of the system that
contains the ESN.
3. When the ESN is part of a HomeWorks or myRoom system, then the #AREA and #OUTPUT commands found in the
Quantum “System Commands” section of this integration document should be used.
Action Numbers and Parameters:
Action Action Number Parameters
Report (~) Occupied or Closed
1
3 None
Report (~) Unoccupied or Open
1
4 None
Set (#) or Get (?) Current Scene 7 Scene
Set (#) or Get (?) Light Level 14
Level = 0 –100 or 0.00 –100.00
Fade
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Delay
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Set (#) Start Raising 18 None
Set (#) Start Lowering 19 None
Set (#) Stop Raising or Lowering 20 None
NOTES
1. MQSE-4S1-D only
2. The Fade and Delay time are optional. When not used, the system will use a one-second fade time with zero-second delay.
3. Fractional seconds “SS.ss” will be rounded down to the nearest quarter-second. For example, if a fade time is specified
as 1.31 seconds, a value of 1.25 seconds will be used.
NOTE
1. Not Supported in HomeWorks QS / myRoom plus.
myRoom
MQSE-4S1-D
100
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
1 2 3 4
CCI COM
CCO N.O.
CCO COM
24 V
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
100
-
240 V~ 1 A
120
-
240 V~ 1 AX, 1 FLA
/
6 LRA
IEC PELV
/
NECR Class 2
24 V- 132 mA
4,4 in-lb
0,5 N
•
m
65
/
75 °C
Cu
Al
N N N N N N
M
LL
HomeWorks QS
LQSE-4A1-D
120
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
COM
MUX
MUX
Zn. 1Prog. Zn. 2Zn. 3Zn. 4
NNNN
120
-
240 V~ 1 A
DL1DL2 DL3DL4
CCI COM
CCI
N
L