Installation Manual
94
Lutron integration protocol
OUTPUT Command Format
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) or Get (?) Zone Level
Set (#) or Get (?) CCO State
1
1 Level = 0 –100 or 0.00 –100.00
Fade
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
maximum 4 hours
Delay
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
maximum 4 hours
Set (#) Start Raising 2 None
Set (#) Start Lowering 3 None
Set (#)
Stop Raising or Lowering
4 None
Set (#)
Pulse CCO
1
6 None
NOTES
1. Low-capacity switching only.
2. The Fade and Delay time are optional. When not used, the system will use a one-second fade time with zero-second delay.
3. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a fade time is specified
as 1.31 seconds a value of 1.25 seconds will be used.
Example OUTPUT Commands
Operation Command String
Execute: #OUTPUT, Integration ID, Action Number, Parameters
Set dimmer to 75% with a 1 min 30 sec fade. #OUTPUT,1,1,75,01:30<CR><LF>
Start Raising zone level. #OUTPUT,1,2<CR><LF>
Stop Raising / Lowering zone level. #OUTPUT,1,4<CR><LF>
Query: ?OUTPUT, Integration ID, Action Number
What is the state of the output? ?OUTPUT,1,1<CR><LF>
Response
1
: ~OUTPUT, Integration ID, Action Number, Parameters
Output level is set to 90%. ~OUTPUT,1,1,90.00<CR><LF>
NOTE
1. The system will report the target level of a dimmer while it is fading from one level to another.
The actual level is not transmitted while dimming between levels.
Example: If the “Over Sink” (Integration ID-1) dimmer is at 20% and is then commanded to go to 100% by sending
#OUTPUT,1,1,100, the response from the system will be ~OUTPUT,1,1,100.00
Low-Capacity Switching/Phase-Adaptive
DIN Power Module (1A/output) (continued)
OUTPUT Commands
Operation
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Command
Integration ID (example)
#OUTPUT, 1, Action Number, Parameters
myRoom
MQSE-4S1-D
100
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
1 2 3 4
CCI COM
CCO N.O.
CCO COM
24 V
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
100
-
240 V~ 1 A
120
-
240 V~ 1 AX, 1 FLA
/
6 LRA
IEC PELV
/
NECR Class 2
24 V- 132 mA
4,4 in-lb
0,5 N
•
m
65
/
75 °C
Cu
Al
N N N N N N
M
LL
HomeWorks QS
LQSE-4A1-D
120
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
COM
MUX
MUX
Zn. 1Prog. Zn. 2Zn. 3Zn. 4
NNNN
120
-
240 V~ 1 A
DL1DL2 DL3DL4
CCI COM
CCI
N
L