Installation Manual
Table Of Contents
- Table of Contents
- About Integration
- Stanza
- QS Standalone
- RadioRA 2
- Quantum
- HomeWorks QS
- Devices
- Stanza Keypads
- Tabletop Stanza Keypads
- Stanza Dimmers
- Stanza Switch
- Stanza Lamp Module
- Stanza Input/Output Interface
- GRAFIK Eye QS
- Energi Savr Node QS/DALI
- Energi Savr Node QS/Int'l 0-10V
- Energi Savr Node QS/EcoSystem
- Energi Savr Node QS/0-10V
- seeTouch QS Keypads
- seeTouch QS Int'l Keypads
- Sivoia QS Shades
- Sivoia QS Venetian Blinds
- Maestro Dimmers
- Hybrid Keypad
- Tabletop seeTouch Keypads
- Pico Wireless Controls
- Visor Control Receiver
- Radio Powr Savr
- HVAC Controller
- Wireless Temperature Sensor
- Dynamic Keypad
- Programmers Appendix
- Contact Information
102
Lutron® integration protocol
Sivoia® QS Shades: OUTPUT Commands
OUTPUT Command Format
#OUTPUT, 1, Action Number, Parameters
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) or Get (?) Zone
Level
1 Level
2
= 0–100 or 0.00–100.00,
1
Fade
3
in SS.ss
4
, SS, MM:SS, or HH:MM:SS
Delay
5
in SS.ss
4
, SS, MM:SS, or HH:MM:SS
Start Raising 2 None
Start Lowering 3 None
Stop Raising/Lowering
4 None
Example OUTPUT Messages
Examples presume shade has been assigned Integration ID 1.
Operation Command String
Execute: #OUTPUT, Integration ID, Action Number, Parameters
Set dimmer to 75% with a 1 min 30 sec delay. #OUTPUT,1,1,75,0,1:30<CR><LF>
Start Raising shade level. #OUTPUT,1,2<CR><LF>
Stop Raising/Lowering shade level. #OUTPUT,1,4<CR><LF>
Query: ?OUTPUT, Integration ID, Action Number
What is the state of the output? ?OUTPUT,1,1<CR><LF>
Response
6
: ~OUTPUT, Integration ID, Action Number, Parameters
Output level is set to 90%. ~OUTPUT,1,1,90.00<CR><LF>
NOTES
1. 0% = Closed; 100% = Open
2.
For shades, a level of 0 (or 0.00) equals closed and a level of 100 (or 100.00) equals full open.
3.
Fade is not available for shades since they move at a constant rate. The parameter must be entered
but is ignored.
4. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a
delay time is specified as 1.45 seconds a value of 1.25 seconds will be used.
5. The Delay time is optional. When not used, the system will use a zero second delay. The minimum
delay time is 0.25 seconds. The maximum delay time is 4 hours. Not supported in QS Standalone.
6. The system will report the target level of a shade. The actual level is not transmitted while they are
moving.
Example: If the Living Room Blackouts (Integration ID 1) are at 20% and are commanded to go to
100% by sending
#OUTPUT, 1, 1, 100 the response from the system will be ~OUTPUT, 1, 1, 100.00
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)