Installation Manual

104
Lutron® integration protocol
Sivoia® QS Venetian Blinds: OUTPUT Commands
OUTPUT Command Format
#OUTPUT, 1, Action Number, Parameters
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) or Get (?)
Venetian lift level only
1 Lift Level
1
= 0–100 or 0.00–100.00
1
Fade
2
in SS.ss
3
, SS, MM:SS, or HH:MM:SS
Delay
4
in SS.ss
3
, SS, MM:SS, or HH:MM:SS
Set (#) or Get (?)
Venetian tilt level only
9 Tilt Level
1
= 0–100 or 0.00–100.00
1
Fade
2
in SS.ss
3
, SS, MM:SS, or HH:MM:SS
Delay
4
in SS.ss
3
, SS, MM:SS, or HH:MM:SS
Set (#) or Get (?)
Venetian lift & tilt level
10 Lift Level
1
= 0–100 or 0.00–100.00
1
Tilt Level
1
= 0–100 or 0.00–100.00
1
Fade
2
in SS.ss
3
, SS, MM:SS, or HH:MM:SS
Delay
4
in SS.ss
3
, SS, MM:SS, or HH:MM:SS
Start raising Venetian tilt
11 None
Start lowering Venetian tilt
12 None
Stop Venetian tilt
13 None
Start raising Venetian lift
14 None
Start lowering Venetian lift
15 None
Stop Venetian lift
16 None
Example OUTPUT Messages
Examples presume shade has been assigned Integration ID 1.
Operation Command String
Execute: #OUTPUT, Integration ID, Action Number, Parameters
Set Venetian blind to lift 0%, tilt 50% #OUTPUT,1,10,0,50<CR><LF>
Start raising Venetian tilt. #OUTPUT,1,11<CR><LF>
Stop raising Venetian tilt. #OUTPUT,1,13<CR><LF>
Query: ?OUTPUT, Integration ID, Action Number
What is the state of the Venetian lift and tilt? ?OUTPUT,1,10<CR><LF>
Response
5
: ~OUTPUT, Integration ID, Action Number, Parameters
Venetian lift level is 0%, tilt level 50%. ~OUTPUT,1,10,0.00,50.00<CR><LF>
Notes appear on following page...
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)