PGM
11
Lutron® integration protocol
MONITORING Command Formats
MONITORING Command-specific fields
Monitoring Type:
Description Monitoring Type
Diagnostic Monitoring 1
Button Monitoring 3
LED State Monitoring 4
Zone Level Monitoring 5
Reply State
(if disabled, all messages FROM the integration access point will cease)
11
Prompt State (if disabled, the prompt will not be printed to the terminal) 12
Set (#) or Get (?) State of All Monitoring
(except Reply and Prompt)
255
Action Numbers:
Action Action Number
Enable 1
Disable 2
Example MONITORING Messages
Operation Command String
Execute: #MONITORING, Monitoring Type, Action Number
Disable Diagnostic Monitoring. #MONITORING,1,2<CR><LF>
Enable Button Monitoring. #MONITORING,3,1<CR><LF>
Query: ?MONITORING, Monitoring Type
Is Diagnostic Monitoring disabled? ?MONITORING,1<CR><LF>
Response: ~MONITORING, Monitoring Type, Action Number
Diagnostic Monitoring is disabled. ~MONITORING,1,2<CR><LF>
Use “MONITORING Command-specific fields” tables
to complete these command fields.
Operation
Command
#MONITORING, Monitoring Type, Action Number
SZ-CI-PRG: MONITORING Commands
Stanza
® System Commands (continued)