124
Lutron® integration protocol
Radio Powr SavrTM: DEVICE Commands
DEVICE Command Formats
DEVICE Command-specific fields
•
Component Number:
Component Component Number Available Actions
Occupied State 2 Press (occupied), Release (unoccupied)
~DEVICE, 19, 2, Action Number
Occupied state component
is always 2 for sensors
Operation
Command
Integration ID (example)
•
Action Numbers:
Action Action Number
Press (occupied) 3
Release (unoccupied) 4
Example DEVICE Commands
Examples presume sensor has been assigned Integration ID 19.
Operation Command String
Response: ~DEVICE, Integration ID, Component Number, Action Number, Parameters
Radio Powr Savr 19 went occupied. ~DEVICE,19,2,3<CR><LF>