Installation Manual

130
Lutron® integration protocol
Dynamic Keypad: DEVICE Commands
DEVICE Command Formats
DEVICE Command-specific fields
Component Number:
Component Component Number Available Actions
Button 1 (left hard button) 1 Press, Release
Button 2 (middle hard but-
ton)
2 Press, Release
Button 3 (right hard button) 3 Press, Release
Button N
* N Press, Release
LED M
* M Set or Get LED state
NOTE: Component Numbers for the various pages of buttons and LEDs for a Dynamic Keypad are generated by the
HomeWorksR QS Software.
Action Numbers and Parameters:
Action Action Number Parameters
Press 3 None
Release 4 None
Hold 5 None
Multi-tap 6 None
Set (#) or Get (?) LED State 9 0=Off
1=On
2=Normal-Flash
3=Rapid-Flash
#DEVICE, 2, Component Number, Action Number, Parameters
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
Example DEVICE Commands
Examples presume the Dynamic Keypad has been assigned Integration ID 23.
Operation Command String
Execute: #DEVICE, Integration ID, Component Number, Action Number, Parameters
Press Button 118. #DEVICE,23,118,3<CR><LF>
Turn on LED 566. #DEVICE,23,566,9,1<CR><LF>
Query: ?DEVICE, Integration ID, Component Number, Action Number
What is the state of LED 566? ?DEVICE,23,566,9<CR><LF>
Response: ~DEVICE, Integration ID, Component Number, Action Number, Parameters
LED 1 is on. ~DEVICE,23,566,9,1<CR><LF>