Installation Manual

22
Lutron® integration protocol
PROGRAMING Command Formats
PROGRAMMING Command-specific fields
Configuration Number
Description Action # Parameters
Display programming of a specific
phantom button
NOTE: To display programming of all phantom
buttons, leave the button # field blank
None None
Display Stop-If-Moving configuration of a
specific phantom button
NOTE: To display Stop-If-Moving configuration of
all phantom buttons, use button #0
4 None
Example PROGRAMMING Commands
The following examples show how to verify the programming of the phantom buttons of a QSE-CI-
NWK-E with an Integration ID of "1".
Operation Command String
Display programming of phantom button 1 ?PROGRAMMING,1,1<CR><LF>
Display programming of all phantom buttons ?PROGRAMMING,1<CR><LF>
Display Stop-If-Moving configuration of
phantom button 5
?PROGRAMMING,1,5,4<CR><LF>
Display Stop-If-Moving configuration of all
phantom buttons
?PROGRAMMING,1,0,4<CR><LF>
Operation
Command
?PROGRAMMING, 1, Button#, Action#
QSE-CI-NWK-E: PROGRAMMING Commands
Con/Act
FD/Col
DATA RX
DATA TX
RS232 RX
RS232 TX
LNK/ACT
PWR
1 2 3 4
1 2 3 4 5 6 7 8
QSE-CI-NWK-E
24 V 100 mA
800.523.9466
1.610.282.3800
www.lutron.com/qs
QS Link
QS Standalone System Commands (continued)
Integration ID or Serial # of
the QSE-CI-NWK being used
See table
below
Phantom Button #
(can be 1-100)