Installation Manual

23
Lutron® integration protocol
DEVICE Command Formats
DEVICE Command-specific fields
Actions
Description Action # Parameters
Activate the phantom button preset 3 None
Set a custom level of the shades programmed
to the phantom button
14
1
Level - The level the shades will go to
1
Raise the shades and venetians 18
2
None
Lower the shades and venetians 19
2
None
Stop the shades and venetians 20 None
Set a custom lift and tilt level of venetian blinds
programmed to the phantom button
23
1
Lift level %
Tilt level %
Set a custom lift level only of venetian blinds
programmed to the phantom button
24
1
Lift level %
Set a custom tilt level only of venetian blinds
programmed to the phantom button
25
1
Tilt level %
NOTES
1. Specifying a custom level above will not affect the preset level programmed for the phantom button.
2. For Venetian blinds, the Raise & Lower Actions will affect either the lift or the tilt based on how the phantom button was
programmed. If #PROGRAMMING Action 5 is used (affecting both lift and tilt levels), then the Raise & Lower Actions will
affect the tilt.
NOTE: Programming and device commands require version 8.0 or higher of the NWK software.
Example DEVICE Commands
The following examples show how we can activate phantom buttons on a link with a QSE-CI-NWK-E whose
Integration ID is "1".
Operation Command String
Activate Preset on phantom button 1
#DEVICE,1,1,3<CR> <LF>
Set the level of all shades programmed to phantom button 2 to 50%
#DEVICE,1,2,14,50<CR><LF>
Set all venetian blinds programmed to phantom button 3 to a lift level
of 50% and tilt level of 25%
#DEVICE,1,3,23,50,25<CR><LF>
Set all venetian blinds programmed to phantom button 4 to a lift level of 50%
#DEVICE,1,4,24,50<CR><LF>
Set all venetian blinds programmed to phantom button 5 to a tilt level of 25%
#DEVICE,1,5,25,25<CR><LF>
Raise the shades and venetian blinds programmed to phantom button 6
#DEVICE,1,6,18<CR><LF>
Lower shades and venetian blinds programmed to phantom button 7
#DEVICE,1,7,19<CR><LF>
Stop shades and venetian blinds programmed to phantom button 8
#DEVICE,1,8,20<CR><LF>
Operation
Command
#DEVICE, 1, Button#, Action#, Parameters
QSE-CI-NWK-E: DEVICE Commands
Con/Act
FD/Col
DATA RX
DATA TX
RS232 RX
RS232 TX
LNK/ACT
PWR
1 2 3 4
1 2 3 4 5 6 7 8
QSE-CI-NWK-E
24 V 100 mA
800.523.9466
1.610.282.3800
www.lutron.com/qs
QS Link
QS Standalone System Commands (continued)
Integration ID or Serial # of
the QSE-CI-NWK being used
See table
below
Phantom Button #
(can be 1-100)