Installation Manual
Table Of Contents
- Table of Contents
- About Integration
- Stanza
- QS Standalone
- RadioRA 2
- Quantum
- HomeWorks QS
- Devices
- Stanza Keypads
- Tabletop Stanza Keypads
- Stanza Dimmers
- Stanza Switch
- Stanza Lamp Module
- Stanza Input/Output Interface
- GRAFIK Eye QS
- Energi Savr Node QS/DALI
- Energi Savr Node QS/Int'l 0-10V
- Energi Savr Node QS/EcoSystem
- Energi Savr Node QS/0-10V
- seeTouch QS Keypads
- seeTouch QS Int'l Keypads
- Sivoia QS Shades
- Sivoia QS Venetian Blinds
- Maestro Dimmers
- Hybrid Keypad
- Tabletop seeTouch Keypads
- Pico Wireless Controls
- Visor Control Receiver
- Radio Powr Savr
- HVAC Controller
- Wireless Temperature Sensor
- Dynamic Keypad
- Programmers Appendix
- Contact Information
28
Lutron® integration protocol
RR-MAIN-REP-WH: DEVICE Commands
DEVICE Command Formats
DEVICE Command-specific fields
•
Component Number:
Component Component Number Available Actions
Button 1–100 1-100 Press, Release
LED 1–100 101-200 Set or Get LED state
•
Action Numbers and Parameters:
Action Action Number Parameters
Press 3 None
Release 4 None
Set or Get LED State 9 0=Off
1=On
Example DEVICE Commands
Operation Command String
Execute: #DEVICE, Integration ID, Component Number, Action Number, Parameters
Press Button 1. #DEVICE,4,1,3<CR><LF>
Release Button 1 #DEVICE,4,1,4<CR><LF>
Turn on LED 1. #DEVICE,4,101,9<CR><LF>
Query: ?DEVICE, Integration ID, Component Number, Action Number
What is the state of LED 1? ?DEVICE,4,101,9<CR><LF>
Response: ~DEVICE, Integration ID, Component Number, Action Number, Parameters
LED 1 is on. ~DEVICE,4,101,9,1<CR><LF>
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE, 1, Component Number, Action Number, Parameters
Setup
Wired
RF
Communication
Repeater Status
1
3
4
2
M
Main Repeater
Power
Repeater Link
COM
9 V
1
N / C
MUX
MUX
2
3
4
AddTest
Integrate
Program / Integrate
RS232
Ethernet
USB
RadioRA® 2 System Commands