Installation Manual
Table Of Contents
- Table of Contents
- About Integration
- Stanza
- QS Standalone
- RadioRA 2
- Quantum
- HomeWorks QS
- Devices
- Stanza Keypads
- Tabletop Stanza Keypads
- Stanza Dimmers
- Stanza Switch
- Stanza Lamp Module
- Stanza Input/Output Interface
- GRAFIK Eye QS
- Energi Savr Node QS/DALI
- Energi Savr Node QS/Int'l 0-10V
- Energi Savr Node QS/EcoSystem
- Energi Savr Node QS/0-10V
- seeTouch QS Keypads
- seeTouch QS Int'l Keypads
- Sivoia QS Shades
- Sivoia QS Venetian Blinds
- Maestro Dimmers
- Hybrid Keypad
- Tabletop seeTouch Keypads
- Pico Wireless Controls
- Visor Control Receiver
- Radio Powr Savr
- HVAC Controller
- Wireless Temperature Sensor
- Dynamic Keypad
- Programmers Appendix
- Contact Information
29
Lutron® integration protocol
RR-MAIN-REP-WH: MONITORING Commands
MONITORING Command Formats
MONITORING Command-specific fields
•
Monitoring Type:
Description Monitoring Type
Diagnostic Monitoring 1
Button Monitoring (if enabled, button actions will be reported) 3
LED Monitoring (if enabled, LED states will be reported) 4
Zone Monitoring (if enabled, zone levels will be reported, i.e. dimmer, shade,
contact closure output level)
5
Reply State
(if disabled, all messages FROM the integration access point will cease)
11
Prompt State (if disabled, the prompt will not be printed to the terminal) 12
Set or Get State of All Monitoring (except Reply and Prompt) 255
•
Action Numbers:
Action Action Number
Enable 1
Disable 2
Example MONITORING Commands
Operation Command String
Execute: #MONITORING, Monitoring Type, Action Number
Disable Diagnostic Monitoring. #MONITORING,1,2<CR><LF>
Enable Event Monitoring. #MONITORING,2,1<CR><LF>
Query: ?MONITORING, Monitoring Type
Is Diagnostic Monitoring disabled? ?MONITORING,1<CR><LF>
Response: ~MONITORING, Monitoring Type, Action Number
Diagnostic Monitoring is disabled. ~MONITORING,1,2<CR><LF>
Use “MONITORING Command-specific fields” tables
to complete these command fields.
Operation
Command
#MONITORING, Monitoring Type, Action Number
Setup
Wired
RF
Communication
Repeater Status
1
3
4
2
M
Main Repeater
Power
Repeater Link
COM
9 V
1
N / C
MUX
MUX
2
3
4
AddTest
Integrate
Program / Integrate
RS232
Ethernet
USB