Installation Manual

32
Lutron® integration protocol
Connection Information
Provides an RS232 and Ethernet connection to communicate with external equipment.
RS232
The RS232 connection has the following communication settings:
Baud Rate 9600/19200/38400/115200 (set via dipswitch on unit)
8 data bits
No parity bit
1 stop bit
No flow control
Ethernet
Configuring the control interface to communicate over a network takes not only knowledge of
the Quantum
® system, but of networking as well. Installers with limited networking knowledge
are advised to contact a networking professional before attempting to connect a QSE-CI-NWK-E
through a network. The information below will help an installer communicate the QSE-CI-NWK-E
configurations to a network professional.
The installer will make any necessary changes to the control interface using the Lutron® DeviceIP or
Quantum PC software tool and the network professional can make any necessary changes to the
networking equipment.
Single Ethernet Port
IEEE® 802.3 Auto-Sensing 10BaseT / 100BaseTX
Supports MDI/MDIX auto-crossover (no crossover cable needed).
Female 8P8C “Computer RJ-45” socket
Green Connect LED, Amber Activity LED
Use Cat 5 cabling or better
TCP / IP Settings
IP Address: <static default = 192.168.250.1>
Subnet Mask: < static default = 255.255.255.0>
Gateway: <static default = 0.0.0.0>
Protocols Used for Integration
TELNET
Telnet Server
Used by third party equipment (i.e. touch screen)
Limited to transferring ASCII characters
Telnet Port number is 23
Login #1: nwk
Login #2: nwk2
Con/Act
FD/Col
DATA RX
DATA TX
RS232 RX
RS232 TX
LNK/ACT
PWR
1 2 3 4
1 2 3 4 5 6 7 8
QSE-CI-NWK-E
24 V 100 mA
800.523.9466
1.610.282.3800
www.lutron.com/qs
QS Link
Quantum® Integration Access Points (continued)