Lutron® integration protocol
Con/Act
FD/Col
DATA RX
DATA TX
RS232 RX
RS232 TX
LNK/ACT
PWR
1 2 3 4
1 2 3 4 5 6 7 8
QSE-CI-NWK-E
24 V 100 mA
800.523.9466
1.610.282.3800
www.lutron.com/qs
QS Link
QSE-CI-NWK-E: MONITORING Commands
MONITORING Command Formats
MONITORING Command-specific fields
Monitoring Type:
Description Monitoring Type
Diagnostic Monitoring 1
Event Monitoring 2
Button Monitoring 3
LED State Monitoring 4
Zone Level Monitoring 5
Occupancy Monitoring 6
Area Scene, Device Scene and Shade Group Preset Number Monitoring 8
Reply State
(if disabled, all messages FROM the integration access point will cease)
11
Prompt State (if disabled, the prompt will not be printed to the terminal) 12
Action Numbers:
Action Action Number
Enable 1
Disable 2
Example MONITORING Messages
Operation Command String
Execute: #MONITORING, Monitoring Type, Action Number
Disable Diagnostic Monitoring. #MONITORING,1,2<CR><LF>
Enable Button Monitoring. #MONITORING,5,1<CR><LF>
Query: ?MONITORING, Monitoring Type
Is Button Monitoring enabled? ?MONITORING,3<CR><LF>
Response: ~MONITORING, Monitoring Type, Action Number
Button Monitoring is enabled. ~MONITORING,3,1<CR><LF>
Use “MONITORING Command-specific fields” tables
to complete these command fields.
Operation
Command
#MONITORING, Monitoring Type, Action Number
Quantum® System Commands