Installation Manual
Table Of Contents
- Table of Contents
- About Integration
- Stanza
- QS Standalone
- RadioRA 2
- Quantum
- HomeWorks QS
- Devices
- Stanza Keypads
- Tabletop Stanza Keypads
- Stanza Dimmers
- Stanza Switch
- Stanza Lamp Module
- Stanza Input/Output Interface
- GRAFIK Eye QS
- Energi Savr Node QS/DALI
- Energi Savr Node QS/Int'l 0-10V
- Energi Savr Node QS/EcoSystem
- Energi Savr Node QS/0-10V
- seeTouch QS Keypads
- seeTouch QS Int'l Keypads
- Sivoia QS Shades
- Sivoia QS Venetian Blinds
- Maestro Dimmers
- Hybrid Keypad
- Tabletop seeTouch Keypads
- Pico Wireless Controls
- Visor Control Receiver
- Radio Powr Savr
- HVAC Controller
- Wireless Temperature Sensor
- Dynamic Keypad
- Programmers Appendix
- Contact Information
40
Lutron® integration protocol
SHADEGRP Command Formats
Use “SHADEGRP Command-specific fields” tables
to complete these command fields.
Operation
Command
#SHADEGRP
1
, 2, Action Number, Parameters
Integration ID (example)
SHADEGRP Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) Shade Group
Level
1 Level
2
= 0–100 or 0.00–100.00,
Delay
3
in SS.ss
4
, SS, MM:SS, or HH:MM:SS
4
Raise
5
2 None
Lower
5
3 None
Stop Raise/Lower 4 None
Set or Get Current
Preset
6 Preset Number
6
= 0-30
Example SHADEGRP Messages
Operation Command String
Execute: #SHADEGRP, Integration ID, Action Number, Parameters
Set shade group to 70% (Delay = 2 sec) #SHADEGRP,2,1,70,2<CR><LF>
Lower shade group. #SHADEGRP,2,3<CR><LF>
Query: ?SHADEGRP, Integration ID, Action Number
What is the current active preset? ?SHADEGRP,2,6<CR><LF>
Response: ~SHADEGRP, Integration ID, Action Number, Parameters
Shade group Preset 2 is currently active. ~SHADEGRP,2,6,2<CR><LF>
NOTES
1. SHADEGRP can only be used to control shade groups of a Quantum system that have been
assigned to a particular integration access point. Please refer to the Q-Design
TM software
(Integration Tab) or Quantum Integration Report for details of what shade groups are available for
control and monitoring.
2. The Level is accepted as a percentage, where 100% is fully open and 0% is fully closed.
3. The Delay time is optional. When not used the system will use a zero second delay. The minimum
delay time is 0 seconds. The maximum delay time is 4 hours.
4. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a
delay time is specified as 1.45 seconds a value of 1.25 seconds will be used.
5. When a Raise / Lower command is issued, the shade group’s level will continue to go towards
open / close until a Stop command is received.
6. Preset 0 is the Open Preset and Preset 30 is the Closed Preset.
Quantum® System Commands (continued)
QSE-CI-NWK-E: SHADEGRP Commands
Con/Act
FD/Col
DATA RX
DATA TX
RS232 RX
RS232 TX
LNK/ACT
PWR
1 2 3 4
1 2 3 4 5 6 7 8
QSE-CI-NWK-E
24 V 100 mA
800.523.9466
1.610.282.3800
www.lutron.com/qs
QS Link