Installation Manual

41
Lutron® integration protocol
OUTPUT Command Format
#OUTPUT
1
, 2, Action Number, Parameters
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) or Get (?) Output
Level
1 Level
2
= 0–100 or 0.00–100.00,
Fade
3
in SS.ss
4
, SS, MM:SS
4
, or HH:MM:SS
4
Delay
3
in SS.ss
4
, SS, MM:SS
4
, or HH:MM:SS
4
Raise
5
2 None
Lower
5
3 None
Stop Raise/Lower
5
4 None
Pulse 6 Pulse
6
time in SS.ss
4
, MM:SS.ss
4
, or
HH:MM:SS.ss
4
, or
Delay
3
in SS.ss
4
, SS, MM:SS
4
, or HH:MM:SS
4
Example OUTPUT Messages
Operation Command String
Execute: #OUTPUT, Integration ID, Action Number, Parameters
Set output level to 70% (Fade = 4 sec, Delay =
2 sec)
#OUTPUT,2,1,70,4,2<CR><LF>
Raise Output #OUTPUT,2,2<CR><LF>
Query: ?OUTPUT, Integration ID
What is the current output level? ?OUTPUT,2<CR><LF>
Response
3
: ~OUTPUT, Integration ID, Action Number, Parameters
Output level is set to 48%. ~OUTPUT,2,1,48<CR><LF>
NOTES
1. OUTPUT commands can be used to control system lighting zones, individual shades, and contact
closed outputs.
2. The Level is taken as a percentage.
3. The Fade and Delay time are optional. When not used the system will use a one second fade time
with zero second delay. The minimum fade and delay time is 0 seconds. The maximum fade and
delay time is 4 hours. For shade outputs, the Fade parameter has no effect (since shades have
fixed speeds) but it is required when specifying an optional delay.
4. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a
fade time is specified as 1.45 seconds a value of 1.25 seconds will be used.
5. When a Raise / Lower command is issued, the output’s level will continue to go towards high end /
low end until a Stop command is received.
6. The default time is one second.
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
Quantum® System Commands (continued)
QSE-CI-NWK-E: OUTPUT Commands
Con/Act
FD/Col
DATA RX
DATA TX
RS232 RX
RS232 TX
LNK/ACT
PWR
1 2 3 4
1 2 3 4 5 6 7 8
QSE-CI-NWK-E
24 V 100 mA
800.523.9466
1.610.282.3800
www.lutron.com/qs
QS Link