Installation Manual

47
Lutron® integration protocol
OUTPUT Command Format
#OUTPUT
1
, 2, Action Number, Parameters
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) or Get (?) Output Level 1 Level
2
= 0–100 or 0.00–100.00,
Fade
3
in SS.ss
4
, SS, MM:SS
4
, or HH:MM:SS
4
Delay
3
in SS.ss
4
, SS, MM:SS
4
, or HH:MM:SS
4
Raise
5
2 None
Lower
5
3 None
Stop Raise/Lower
5
4 None
Flash (#) or Get (?) Flash
Frequency
5 Fade
3
in SS.ss
4
, SS, MM:SS
4
, or HH:MM:SS
4
Delay
3
in SS.ss
4
, SS, MM:SS
4
, or HH:MM:SS
4
Set Pulse CCO (#) 6 Pulse
6
time in SS.ss
4
, MM:SS.ss
4
, or
HH:MM:SS.ss
4
, or
Delay
3
in SS.ss
4
, SS, MM:SS
4
, or HH:MM:SS
4
Set (#) Venetian Shade Tilt to
a specified level
9 Tilt level in % = 0.00-100
Delay
3
in SS.ss
4
, SS, MM:SS
4
, or HH:MM:SS
4
,
or HH:MM:SS.ss
Set (#) Venetian Shade Tilt
and Lift to a specified level
10 Lift
2
= 0–100 or 0.00–100.00,
Tilt
2
= 0–100 or 0.00–100.00,
Fade
3
in SS.ss, SS, MM:SS, or HH:MM:SS
4
Delay
3
in SS.ss, SS, MM:SS, or HH:MM:SS
4
Raise (#) Tilt Output Level 11 None
Lower (#) Tilt Output Level 12 None
Stop (#) Raise/Lower Tilt
Output Level
13 None
Raise(#) Lift Output Level 14 None
Lower(#) Lift Output Level 15 None
Stop (#) Raise/Lower Lift
Output Level
16 None
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
HomeWorks® QS System Commands
HQP6-2-120: OUTPUT Commands