Installation Manual
Table Of Contents
- Table of Contents
- About Integration
- Stanza
- QS Standalone
- RadioRA 2
- Quantum
- HomeWorks QS
- Devices
- Stanza Keypads
- Tabletop Stanza Keypads
- Stanza Dimmers
- Stanza Switch
- Stanza Lamp Module
- Stanza Input/Output Interface
- GRAFIK Eye QS
- Energi Savr Node QS/DALI
- Energi Savr Node QS/Int'l 0-10V
- Energi Savr Node QS/EcoSystem
- Energi Savr Node QS/0-10V
- seeTouch QS Keypads
- seeTouch QS Int'l Keypads
- Sivoia QS Shades
- Sivoia QS Venetian Blinds
- Maestro Dimmers
- Hybrid Keypad
- Tabletop seeTouch Keypads
- Pico Wireless Controls
- Visor Control Receiver
- Radio Powr Savr
- HVAC Controller
- Wireless Temperature Sensor
- Dynamic Keypad
- Programmers Appendix
- Contact Information
58
Lutron® integration protocol
ETHERNET Command Formats
ETHERNET Command-specific fields
•
Configuration Number
Description Config. Number Parameters
Get (?) or Set(#) IP Address 0 Address (XXX.XXX.XXX.XXX)
Get (?) or Set (#) Gateway
Address
1 Address (XXX.XXX.XXX.XXX)
Get (?) or Set (#) Subnet
Mask
2 Address (XXX.XXX.XXX.XXX)
Get (?) DHCP 4 None
Get (?) or Set (#) Multicast
address
5 Address (XXX.XXX.XXX.XXX)
Example ETHERNET Commands
Operation Command String
Execute: #ETHERNET, Configuration Number, Parameters
Set IP Address to 192.168.250.1 #ETHERNET,0,192.168.250.1<CR><LF>
Set Gateway Address to 10.2.4.1 #ETHERNET,1,10.2.4.1<CR><LF>
Query: ?ETHERNET, Configuration Number, Parameters
What is the IP Address? ?ETHERNET,0<CR><LF>
Response: ~DEVICE, Integration ID, Configuration Number, Parameters
The IP Address is 192.168.250.1 ~ETHERNET,0=,192.168.250.1<CR><LF>
Use “ETHERNET Command-specific fields” tables to
complete these command fields.
Operation
Command
#ETHERNET, Configuration Number, Parameters
HQP6-2-120: ETHERNET Commands
HomeWorks
® QS System Commands (continued)