Installation Manual

62
Lutron® integration protocol
Stanza® Keypads: DEVICE Commands
DEVICE Command Formats
DEVICE Command-specific fields
Component Number:
Component Component Number Available Actions
Button 1 4 Press, Release
Button 2 5 Press, Release
Button 3 6 Press, Release
Button 4 7 Press, Release
Button 5 8 Press, Release
LED 1 15 Get (?) LED state
LED 2 16 Get (?) LED state
LED 3 17 Get (?) LED state
LED 4 18 Get (?) LED state
LED 5 19 Get (?) LED state
Action Numbers and Parameters:
Action Action Number Parameters
Press 3 None
Release 4 None
Get (?) LED state 9 None
#DEVICE, 2, Component Number, Action Number, Parameters
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
Example DEVICE Messages
Examples presume keypad has been assigned Integration ID 2.
Operation Command String
Execute: #DEVICE, Integration ID, Component Number, Action Number, Parameters
Press Button 1. #DEVICE,2,4,3<CR><LF>
Query: ?DEVICE, Integration ID, Component Number, Action Number
What is the state of LED 1? ?DEVICE,2,15,9<CR><LF>
Response: ~DEVICE, Integration ID, Component Number, Action Number, Parameters
LED 1 is on. ~DEVICE,2,15,9,1<CR><LF>
Button 4