Installation Manual

68
Lutron® integration protocol
Stanza® Dimmers: OUTPUT Commands
OUTPUT Command Format
#OUTPUT, 1, Action Number, Parameters
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) or Get (?) Zone
Level
1 Level = 0–100 or 0.00–100.00,
Fade
1
in SS.ss
2
, SS, MM:SS, or HH:MM:SS
Delay
1
in SS.ss
2
, SS, MM:SS, or HH:MM:SS
Example OUTPUT Messages
Examples presume dimmer has been assigned Integration ID 1.
Operation Command String
Execute: #OUTPUT, Integration ID, Action Number, Parameters
Set dimmer to 75% with a 1 min 30 sec fade. #OUTPUT,1,1,75,01:30<CR><LF>
Query: ?OUTPUT, Integration ID, Action Number
What is the state of the output? ?OUTPUT,1,1<CR><LF>
Response
3
: ~OUTPUT, Integration ID, Action Number, Parameters
Output level is set to 90%. ~OUTPUT,1,1,90.00<CR><LF>
NOTES
1. The Fade and Delay time are optional. When not used the system will use a one second fade time
with zero second delay. The minimum fade and delay time is 0.25 seconds. The maximum fade
and delay time is 4 hours.
2. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a
fade time is specified as 1.45 seconds a value of 1.25 seconds will be used.
3. The system will report the target level of dimmers and switches while a fade or delay is in progress.
The actual level is not transmitted while a fade or delay is in progress.
Example: If the “Over Sink” (1) dimmer is at 20% and is then commanded to go to 100% by
sending
#OUTPUT,1,1,100 the response from the system will be ~OUTPUT,1,1,100.00
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)