Installation Manual
Table Of Contents
- Table of Contents
- About Integration
- Stanza
- QS Standalone
- RadioRA 2
- Quantum
- HomeWorks QS
- Devices
- Stanza Keypads
- Tabletop Stanza Keypads
- Stanza Dimmers
- Stanza Switch
- Stanza Lamp Module
- Stanza Input/Output Interface
- GRAFIK Eye QS
- Energi Savr Node QS/DALI
- Energi Savr Node QS/Int'l 0-10V
- Energi Savr Node QS/EcoSystem
- Energi Savr Node QS/0-10V
- seeTouch QS Keypads
- seeTouch QS Int'l Keypads
- Sivoia QS Shades
- Sivoia QS Venetian Blinds
- Maestro Dimmers
- Hybrid Keypad
- Tabletop seeTouch Keypads
- Pico Wireless Controls
- Visor Control Receiver
- Radio Powr Savr
- HVAC Controller
- Wireless Temperature Sensor
- Dynamic Keypad
- Programmers Appendix
- Contact Information
70
Lutron® integration protocol
Stanza® Switch: OUTPUT Commands
OUTPUT Command Format
#OUTPUT, 1, Action Number, Parameters
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) or Get (?) Zone
Level
1 Level
1
= 0–100 or 0.00–100.00,
Fade
2
in SS.ss
3
, SS, MM:SS, or HH:MM:SS
Delay
2
in SS.ss
3
, SS, MM:SS, or HH:MM:SS
Example OUTPUT Messages
Examples presume switch has been assigned Integration ID 1.
Operation Command String
Execute: #OUTPUT, Integration ID, Action Number, Parameters
Set switch to 100% with a 1 min 30 sec fade. #OUTPUT,1,1,100,01:30<CR><LF>
Query: ?OUTPUT, Integration ID, Action Number
What is the state of the output? ?OUTPUT,1,1<CR><LF>
Response
4
: ~OUTPUT, Integration ID, Action Number, Parameters
Output level is set to 100%. ~OUTPUT,1,1,100.00<CR><LF>
NOTES
1. Any level greater than 0 will turn ON the output. When level is equal to 0 the output will turn OFF.
2. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a
fade time is specified as 1.45 seconds a value of 1.25 seconds will be used.
3. For switches, the fade parameter has no effect but it is required when specifying an optional delay.
The minimum fade and delay time is 0.25 seconds. The maximum fade and delay time is 4 hours.
4. The system will report the target level of dimmers and switches while a fade or delay are in
progress. The actual level is not transmitted while a fade or delay are in progress.
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)