Lutron® integration protocol
DEVICE Command-specific fields
Component Number (continued):
Component Component Number Available Actions
Shade Column 1 Open LED 174
Get (?) LED state
Shade Column 1 Preset 1 LED 175
Get (?) LED state
Shade Column 1 Close LED 211
Get (?) LED state
Shade Column 2 Open LED 183
Get (?) LED state
Shade Column 2 Preset 1 LED 184
Get (?) LED state
Shade Column 2 Close LED 220
Get (?) LED state
Shade Column 3 Open LED 192
Get (?) LED state
Shade Column 3 Preset 1 LED 193
Get (?) LED state
Shade Column 3 Close LED 229
Get (?) LED state
Action Numbers and Parameters:
Action Action Number Parameters
Press 3 None
Release 4 None
Set Current Scene 7 Scene
Set (#) or Get (?) LED
State
3
9 0=Off
1=On
2=Normal-Flash: 1 flash every second
3=Rapid-Flash: 10 flashes every second
Set Light Level 14 Level = 0–100 or 0.00–100.00,
Fade in SS.ss
1
, SS, MM:SS, or HH:MM:SS
2
Delay
5
in SS.ss
1
, SS, MM:SS, or HH:MM:SS
2
Set Zone Lock
4
15 0=Off; 1=On
Set Scene Lock
4
16 0=Off; 1=On
Set Sequence State
4
17 0=Off
1=Sequence through Scenes 1-4
2=Sequence through Scenes 5-16
Raise 18 None
Lower 19 None
Stop 20 None
NOTES
The number of zone controllers available matches the number of zones a particular model supports.
1. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a fade time
is specified as 1.31 seconds a value of 1.25 seconds will be used.
2. The Fade and Delay time are optional. When not used, the system will use a one second fade time with zero
second delay.
3. Quantum only. Set is for unprogrammed buttons only.
4. QS Standalone only.
5. Not supported in QS Standalone.
GRAFIK Eye® QS: DEVICE Commands (continued)
1 2 3 4 5 6
Scene 1
OK
Fade Time
03 Seconds