Installation Manual

80
Lutron® integration protocol
DEVICE Command-specific fields
Action Numbers and Parameters:
Component Component Number Available Actions
Zone 1 – Zone 32
1,2,3
201 232 Set or Get Light Level, Raise, Lower, Stop
Area 1 – Area 32
1,3
401 432 Set or Get Scene, Set Light Level, Raise, Lower, Stop
Energi Savr NodeTM QS for DALI
DEVICE Commands
DEVICE Command Formats
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE, 5, Component Number, Action Number, Parameters
NOTES
1. Zones and areas are created and configured using Lutron's ESN Configuration Tool on an iPhone®
or iPod touch
® mobile device, or the Quantum® Q-DesignTM Tool. Only those areas and zones
which have been configured using one of these tools are accessible through integration.
2. Assigned zones can be given an individual Integration ID and controlled using the #OUTPUT
command. For more details on setting the output Integration ID of a zone component, see the
Integration Access Point section of the system that contains the ESN.
3. When the ESN is part of a Quantum system, then the #AREA and #OUTPUT commands found in
the Quantum "System Commands" section of this integration document should be used.
500-13431 Rev. B
N1771
Z096