Installation Manual

86
Lutron® integration protocol
OUTPUT Command Format
#OUTPUT, 1, Action Number, Parameters
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set or Get Zone Level 1 Level = 0–100 or 0.00–100.00,
Fade in SS.ss
1
, SS, MM:SS, or HH:MM:SS
2
Delay
3
in SS.ss
1
, SS, MM:SS, or HH:MM:SS
2
Start Raising 2 None
Start Lowering 3 None
Stop Raising/Lowering
4 None
Example OUTPUT Commands
Operation Command String
Execute: #OUTPUT, Integration ID, Action Number, Parameters
Set dimmer to 75% with a 1 min 30 sec fade. #OUTPUT,1,1,75,01:30<CR><LF>
Start Raising zone level. #OUTPUT,1,2<CR><LF>
Stop Raising/Lowering zone level. #OUTPUT,1,4<CR><LF>
Query: ?OUTPUT, Integration ID, Action Number
What is the state of the output? ?OUTPUT,1,1<CR><LF>
Response
4
: ~OUTPUT, Integration ID, Action Number, Parameters
Output level is set to 90%. ~OUTPUT,1,1,90.00<CR><LF>
NOTES
1. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a
fade time is specified as 1.31 seconds a value of 1.25 seconds will be used.
2. The Fade and Delay time are optional. When not used the system will use a one second fade time
with zero second delay.
3. Not supported in QS Standalone.
4. The system will report the target level of a dimmer while it is fading from one level to another.
The actual level is not transmitted while dimming between levels.
Example: If the “Over Sink” (Integration ID - 1) dimmer is at 20% and is then commanded to go to
100% by sending
#OUTPUT, 1, 1, 100 the response from the system will be ~OUTPUT, 1, 1, 100.00
Energi Savr NodeTM QS for
International 0-10V / Switching
OUTPUT Commands