Installation Manual

88
Lutron® integration protocol
DEVICE Command-specific fields
Action Numbers and Parameters:
Component Component Number Available Actions
Zone 1 – Zone 100
1,2,3
1001 1100 Set or Get Light Level, Raise, Lower, Stop
Area 1 – Area 100
1,3
1201 1300 Set or Get Scene, Set Light Level, Raise, Lower, Stop
Energi Savr NodeTM with EcoSystem®
DEVICE Commands
DEVICE Command Formats
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE, 5, Component Number, Action Number, Parameters
NOTES
1. Zones and areas are created and configured using Lutron's ESN Configuration Tool on an iPhone®
or iPod touch
® mobile device, or the Quantum® Q-DesignTM Tool. Only those areas and zones which
have been configured using one of these tools are accessible through integration.
2. Assigned zones can be given an individual Integration ID and controlled using the #OUTPUT
command. For more details on setting the output Integration ID of a zone component, see the
Integration Access Point section of the system that contains the ESN.
3. When the ESN is part of a Quantum system, then the #AREA and #OUTPUT commands found in
the Quantum "System Commands" section of this integration document should be used.