Installation Manual

89
Lutron® integration protocol
DEVICE Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set Current Scene 7 Scene
Set Light Level 14 Level = 0–100 or 0.00–100.00,
Fade in SS.ss
1
, SS, MM:SS, or HH:MM:SS
2
Delay
3
in SS.ss
1
, SS, MM:SS, or HH:MM:SS
2
Raise 18 None
Lower 19 None
Stop 20 None
NOTES
1. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a
fade time is specified as 1.31 seconds a value of 1.25 seconds will be used.
2. The Fade and Delay time are optional. When not used, the system will use a one second fade time
with zero second delay.
3. Not supported in QS Standalone.
Energi Savr NodeTM with EcoSystem®
DEVICE Commands (continued)