Installation Manual
Table Of Contents
- Table of Contents
- About Integration
- Stanza
- QS Standalone
- RadioRA 2
- Quantum
- HomeWorks QS
- Devices
- Stanza Keypads
- Tabletop Stanza Keypads
- Stanza Dimmers
- Stanza Switch
- Stanza Lamp Module
- Stanza Input/Output Interface
- GRAFIK Eye QS
- Energi Savr Node QS/DALI
- Energi Savr Node QS/Int'l 0-10V
- Energi Savr Node QS/EcoSystem
- Energi Savr Node QS/0-10V
- seeTouch QS Keypads
- seeTouch QS Int'l Keypads
- Sivoia QS Shades
- Sivoia QS Venetian Blinds
- Maestro Dimmers
- Hybrid Keypad
- Tabletop seeTouch Keypads
- Pico Wireless Controls
- Visor Control Receiver
- Radio Powr Savr
- HVAC Controller
- Wireless Temperature Sensor
- Dynamic Keypad
- Programmers Appendix
- Contact Information
92
Lutron® integration protocol
DEVICE Command-specific fields
•
Action Numbers and Parameters:
Component Component Number Available Actions
Zone 1 – Zone 4
1,2,3
5 – 8 Set or Get Light Level, Raise, Lower, Stop
Area 1 – Area 4
1,3
10 – 14 Set or Get Scene, Set Light Level, Raise, Lower, Stop
Energi Savr NodeTM for 0-10V / Switching
DEVICE Commands
DEVICE Command Formats
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE, 5, Component Number, Action Number, Parameters
NOTES
1. Zones and areas are created and configured using Lutron's ESN Configuration Tool on an iPhone®
or iPod touch
® mobile device, or the Quantum® Q-DesignTM Tool. Only those areas and zones
which have been configured using one of these tools are accessible through integration.
2. Assigned zones can be given an individual Integration ID and controlled using the #OUTPUT
command. For more details on setting the output Integration ID of a zone component, see the
Integration Access Point section of the system that contains the ESN.
3. When the ESN is part of a Quantum system, then the #AREA and #OUTPUT commands found in
the Quantum "System Commands" section of this integration document should be used.