Installation Manual
6
Lutron integration protocol
DEVICE Command-specific fields (continued)
Action Numbers and Parameters:
Action Action Number Parameters
Set(#)orGet(?)ZoneLock
1,2,3
15 0=Off
1=On
Set(#)orGet(?)SceneLock
1,2,3
16 0=Off
1=On
Set(#)orGet(?)SequenceState
1,2,3
17 0=Off
1=Scenes1–4
2=Scenes5–16
Set(#)StartRaising
3,4,5
18 None
Set(#)StartLowering
3,4,5
19 None
Set(#)StopRaisingorLowering
3,4,5
20 None
Get(?)batterystatus 22 1=Normal,2=Low
Set(#)acustomliftandtiltlevelofvenetianblinds
programmedtothephantombutton
4,6
23 Liftlevel%
Tiltlevel%
Set(#)acustomliftlevelonlyofvenetianblinds
programmedtothephantombutton
4,6
24 Liftlevel%
Set(#)acustomtiltlevelonlyofvenetianblinds
programmedtothephantombutton
4,6
25 Tiltlevel%
Set(#)HoldorRelease
2
32 None
Set(#)GRAFIKEyeQSTimeclockstate 34 0=Disabled
1=Enabled
Get(?)QueryCCIstate
8
35 None
Set(#)orGet(?)ActiveLEDLevel
7
36 0–100%
Set(#)orGet(?)InactiveLEDLevel
7
37 0–100%
Get(?)SensorTemperature(°F)
9,10,11
41 None
Get(?)SensorTemperature(°C)
9,10,11
42 None
NOTES
1 NotsupportedinHomeWorksQS
2 NotsupportedinRadioRA2
3 NotsupportedbyQuantum
4 UseOUTPUTcommandwithequivalentactionnumberinRadioRA2
5 UseOUTPUTcommandwithequivalentactionnumberinHomeWorksQS
6 UseSHADEGRPcommandwithequivalentactionnumberinHomeWorksQS
7 AppliesonlytoPalladiomkeypads
8 RequiresNWKrmware8 47ornewerforQSStandalonesystems
9 SupportedbyPalladiomThermostatonly
10 Thisfunctionreports“UNKNOWN”ifthevalueisnotknown
11 Whenissuingthiscommand,usetheintegrationIDandcomponentnumberofthetemperaturesensor,not
theHVACzone
Integrator’s Reference (continued)
DEVICE: Command Summary (continued)
Continuedonnextpage…










