Installation Manual
112
Lutron integration protocol
Devices (continued)
Tabletop seeTouch Keypad (continued)
DEVICECommands(continued)
DEVICE Command-specific fields (continued)
Component Numbers (continued):
Component Component Number Available Actions
LED1 81 SetorGetLEDstate
LED2 82 SetorGetLEDstate
LED3 83 SetorGetLEDstate
LED4 84 SetorGetLEDstate
LED5 85 SetorGetLEDstate
LED6 86 SetorGetLEDstate
LED7 87 SetorGetLEDstate
LED8 88 SetorGetLEDstate
LED9 89 SetorGetLEDstate
LED10 90 SetorGetLEDstate
LED11 91 SetorGetLEDstate
LED12 92 SetorGetLEDstate
LED13 93 SetorGetLEDstate
LED14 94 SetorGetLEDstate
LED15 95 SetorGetLEDstate
Action Numbers and Parameters:
Action Action Number Parameters
Set(#)Press 3 None
Set(#)Release 4 None
Set(#)orGet(?)LEDState
Set is for unprogrammed LEDs only
9 0=Off
1=On
Example DEVICE Commands
ExamplespresumekeypadhasbeenassignedIntegrationID3
Operation Command String
Execute: #DEVICE,IntegrationID,ComponentNumber,ActionNumber,Parameters
PressButton1 #DEVICE,3,1,3<CR><LF>
TurnOnLED1 #DEVICE,3,81,9,1<CR><LF>
Query: ?DEVICE,IntegrationID,ComponentNumber,ActionNumber
WhatisthestateofLED1? ?DEVICE,3,81,9<CR><LF>
Response: ~DEVICE,IntegrationID,ComponentNumber,ActionNumber,Parameters
LED1isOn ~DEVICE,3,81,9,1<CR><LF>
Continuedonnextpage…