Installation Manual

114
Lutron integration protocol
Devices (continued)
Pico Wireless Control (continued)
DEVICECommands
DEVICE Command Formats
DEVICE Command-specific fields
Component Numbers:
Component Component Number Available Actions
For all Legacy models and all Current models except for PJ2-4B
Button1 2 Press,Release
Button2 3 Press,Release
Button3 4 Press,Release
ButtonRaise 5 Press,Release
ButtonLower 6 Press,Release
For PJ2-4B model only
Button1 8 Press,Release
Button2 9 Press,Release
Button3 10 Press,Release
Button4 11 Press,Release
Action Numbers and Parameters:
Action Action Number Parameters
Set(#)Press 3 None
Set(#)Release 4 None
Example DEVICE Commands
ExamplespresumePicocontrolhasbeenassignedIntegrationID2
Operation Command String
Execute: #DEVICE,IntegrationID,ComponentNumber,ActionNumber,Parameters
PressButton1(onanon-4Bmodel) #DEVICE,2,2,3<CR><LF>
Response: ~DEVICE,IntegrationID,ComponentNumber,ActionNumber,Parameters
Button1waspressed ~DEVICE,2,2,3<CR><LF>
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE,2,ComponentNumber,ActionNumber,Parameters