Installation Manual
117
Lutron integration protocol
Devices (continued)
Hybrid Keypad (continued)
DEVICECommands(continued)
DEVICE Command-specific fields (continued)
Action Numbers and Parameters:
Action Action Number Parameters
Set(#)Press 3 None
Set(#)Release 4 None
Set(#)orGet(?)LEDState 9 0=Off
1=On
2=Normal-Flash:1asheverysecond
1
3=Rapid-Flash:10asheseverysecond
1
NOTE
1 “Set”isforLEDsonunprogrammedbuttonsandbuttonswithLEDlogic‘DenedbyIntegration ’
Example DEVICE Commands
ExamplespresumekeypadhasbeenassignedIntegrationID2
Operation Command String
Execute: #DEVICE,IntegrationID,ComponentNumber,ActionNumber,Parameters
PressButton1 #DEVICE,2,1,3<CR><LF>
TurnOnLED5 #DEVICE,2,85,9,1<CR><LF>
Query: ?DEVICE,IntegrationID,ComponentNumber,ActionNumber
WhatisthestateofLED1? ?DEVICE,2,81,9<CR><LF>
Response: ~DEVICE,IntegrationID,ComponentNumber,ActionNumber,Parameters
LED1isOn ~DEVICE,2,81,9,1<CR><LF>