Installation Manual

123
Lutron integration protocol
Devices (continued)
Wallbox Input Closure Interface (continued)
DEVICECommands(continued)
DEVICE Command-specific fields (continued)
Action Numbers and Parameters:
Action Action Number Parameters
Set(#)Press 3 None
Set(#)Release 4 None
Set(#)Hold(onlyifinputmodeis
Momentary)
5 None
Set(#)Double-tap 6 None
Set(#)orGet(?)LEDState
1
9 0 = O f f
1 = O n
2=Normal-Flash:1asheverysecond
2
3=Rapid-Flash:10asheseverysecond
2
Set(#)HoldRelease
2
32 None
NOTES
1  Quantum,HomeWorks,ormyRoomplusonly “Set”isforunprogrammedbuttonsandbuttonswithLEDlogic‘Dened
byIntegration ’
2  AvailableonlyonunitsinaQuantum,HomeWorks,ormyRoomplussystem
Example DEVICE Commands
ExamplespresumekeypadhasbeenassignedIntegrationID2
Operation Command String
Execute: #DEVICE,IntegrationID,ComponentNumber,ActionNumber,Parameters
PressButton1 #DEVICE,2,1,3<CR><LF>
TurnOnLED5 #DEVICE,2,85,9,1<CR><LF>
Query: ?DEVICE,IntegrationID,ComponentNumber,ActionNumber
WhatisthestateofLED1? ?DEVICE,2,81,9<CR><LF>
Response: ~DEVICE,IntegrationID,ComponentNumber,ActionNumber,Parameters
LED1isOn ~DEVICE,2,81,9,1<CR><LF>
ON
12
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
COM
QSE-CI-WCI
INPUTS
ENTRADA
ENTRÉES