Installation Manual
126
Lutron integration protocol
SHADEGRP Command Formats
SHADEGRP Command-specific fields
Action NumbersandParameters:
Action Action Number Parameters
Set(#)orGet(?)Shade
GroupLevel
1
1 Level
2
=0–100or0 00 –100 00
Delay
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Set(#)StartRaising
4
2 None
Set(#)StartLowering
4
3 None
Set(#)StopRaisingor
Lowering
4 None
Set(#)orGet(?)
CurrentPreset
6 PresetNumber
5
= 0 – 3 0
Set(#)TiltLevel 14 Level
6
=0–100or0 00 –100 00
Fade
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Delay
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Set(#)LiftandTiltLevels 15 Lift
6
=0–100or0 00 –100 00
Tilt
6
=0–100or0 00 –100 00
Fade
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Delay
2
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
Set(#)StartRaisingTilt
4
16 None
Set(#)StartLoweringTilt
4
17 None
Set(#)StopRaisingor
LoweringTilt
4
18 None
Set(#)StartRaisingLift
4
19 None
Set(#)StartLoweringLift
4
20 None
Set(#)StopRaisingor
LoweringLift
4
21 None
NOTES
1 Get(?)ShadeGroupLevel(actionnumber1)
2 TheFadeandDelaytimeareoptional Forshades,theFadeparameterhasnoeffect(sinceshadeshavexedspeeds)
butitisrequiredwhenspecifyinganoptionaldelay Whennotused,thesystemwilluseazero-seconddelay The
minimumfadeanddelaytimeis0seconds Themaximumfadeanddelaytimeis4hours
3 Fractionalseconds“SS ss”willberoundeddowntothenearestquartersecond Forexample,ifadelaytimeisspecied
as1 45seconds,avalueof1 25secondswillbeused
4 WhenaRaise/Lowercommandisissued,theshadegroup’slevelwillcontinuetogotowardsopen/closeuntilaStop
commandisreceived
5 Preset0istheOpenPresetandPreset30istheClosedPreset
6 TheLevelisacceptedasapercentage,where100%isfullyopenand0%isfullyclosed
Use “SHADEGRP Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#SHADEGRP,2,ActionNumber,Parameters
Devices (continued)
Sivoia QS Shade / Sivoia QS Wireless Shade (continued)
OUTPUTCommands(continued)