Installation Manual

132
Lutron integration protocol
Devices (continued)
Maestro Dimmer and Plug-In Module (continued)
OUTPUTCommands
OUTPUT Command Format
OUTPUT Command-specific fields
Action NumbersandParameters:
Action Action Number Parameters
Set(#)orGet(?)ZoneLevel 1 Level=0–100or0 00 –100 00
Fade
1
in:SS ss
2
,SS,MM:SS,orHH:MM:SS
Delay
1
in:SS ss
2
,SS,MM:SS,orHH:MM:SS
Set(#)StartRaising 2 None
Set(#)StartLowering 3 None
Set(#)
StopRaisingor
Lowering
4 None
Set(#)StartFlashing
3,4,5
5 Fade
1
in:SS ss
2
,SS,MM:SS,orHH:MM:SS
Delay
1
in:SS ss
2
,SS,MM:SS,orHH:MM:SS
NOTES
1  TheFadeandDelaytimeareoptional Whennotused,thesystemwilluseaone-secondfadetimewithzero-seconddelay
2  Fractionalseconds“SS ss”willberoundeddowntothenearestquartersecond Forexample,ifafadetimeisspecied
as1 31secondsavalueof1 25secondswillbeused
3  Thesystemwillnotreportalevelwhiletheoutputisashing,itwillinsteadreportthatitisashing
4  Defaultasheverysecond,unlessfadetimeisspecied(ashperiodis2×fadetime)
5  Tostopadimmerfromashing,sendittoavalidlevel
Example OUTPUT Commands
ExamplespresumedimmerhasbeenassignedIntegrationID1
Operation Command String
Execute: #OUTPUT,IntegrationID,ActionNumber,Parameters
Setdimmerto75%witha1min30secfade #OUTPUT,1,1,75,01:30<CR><LF>
StartRaisingdimmerlevel #OUTPUT,1,2<CR><LF>
StopRaising/Loweringdimmerlevel #OUTPUT,1,4<CR><LF>
Query: ?OUTPUT,IntegrationID,ActionNumber
Whatisthestateoftheoutput? ?OUTPUT,1,1<CR><LF>
Response
1
: ~OUTPUT,IntegrationID,ActionNumber,Parameters
Outputlevelissetto90% ~OUTPUT,1,1,90.00<CR><LF>
NOTE
1  Thesystemwillreportthetargetlevelofadimmerwhileitisfadingfromoneleveltoanother 
Theactuallevelisnottransmittedwhiledimmingbetweenlevels 
Example:Ifthe“OverSink”(1)dimmerisat20%andisthencommandedtogoto100%bysending
#OUTPUT,1,1,100,
theresponsefromthesystemwillbe~OUTPUT,1,1,100.00
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#OUTPUT,1,ActionNumber,Parameters
LUTRON