Installation Manual
134
Lutron integration protocol
Devices (continued)
Maestro Fan Speed Control (continued)
OUTPUTCommands
OUTPUT Command Format
OUTPUT Command-specific fields
Action NumbersandParameters:
Action Action Number Parameters
Set(#)orGet(?)ZoneLevel 1 Levels:
0=Off
1–25%=Low
26–50%=Medium
56–75%=MediumHigh
76–100%=High
Example OUTPUT Commands
ExamplespresumedimmerhasbeenassignedIntegrationID1
Operation Command String
Execute: #OUTPUT,IntegrationID,ActionNumber,Parameters
SetfanspeedtoMediumHigh #OUTPUT,1,1,75<CR><LF>
Query: ?OUTPUT,IntegrationID,ActionNumber
Whatisthestateoftheoutput? ?OUTPUT,1,1<CR><LF>
Response: ~OUTPUT,IntegrationID,ActionNumber,Parameters
OutputlevelissettoHigh ~OUTPUT,1,1,100.00<CR><LF>
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#OUTPUT
1
,1,ActionNumber,Parameters
NOTE
1 SupportedonlyinHomeWorksQS4 0orhigherandRadioRA26 0orhigher