Installation Manual
138
Lutron integration protocol
Devices (continued)
Visor Control Receiver (continued)
OUTPUTCommands
OUTPUT Command Format
OUTPUT Command-specific fields
Action NumbersandParameters:
Action Action Number Parameters
Set(#)orGet(?)OutputState 1 Level
1
=0–100or0 00 –100 00
Set(#)CCOPulseTime 6 Pulse
2
timein:SS ss
3
,SS,MM:SS,orHH:MM:SS,or
Delay
4
in:SS ss
3
,SS,MM:SS,orHH:MM:SS
NOTES
1 Anylevelgreaterthan0willclosetheoutput Whenlevelisequalto0theoutputwillopen
2 Thedefaulttimeisonesecond
3 Fractionalseconds“SS ss”willberoundeddowntothenearestquartersecond Forexample,ifafadetimeisspecied
as1 45secondsavalueof1 25secondswillbeused
4 TheFadeandDelaytimeareoptional Whennotused,thesystemwilluseaone-secondfadetimewithzero-second
delay Theminimumfadeanddelaytimeis0seconds Themaximumfadeanddelaytimeis4hours Forshadeoutputs,
theFadeparameterhasnoeffect(sinceshadeshavexedspeeds)butitisrequiredwhenspecifyinganoptionaldelay
Example OUTPUT Messages
ExamplespresumeCCOhasbeenassignedIntegrationID21
Operation Command String
Set: #OUTPUT,IntegrationID,ActionNumber,Parameters
Setoutputtoopen #OUTPUT,21,1,0<CR><LF>
Setoutputtoclose #OUTPUT,21,1,1<CR><LF>
Query
1
: ?OUTPUT,IntegrationID,ActionNumber
Whatisthestateoftheoutput? ?OUTPUT,21,1<CR><LF>
Response
2
: ~OUTPUT,IntegrationID,ActionNumber
Outputstateisclosed ~OUTPUT,21,1,100.00<CR><LF>
NOTES
1 Momentaryoutputsshouldnotbequeried
2 Thesystemwillreportthetargetlevelofoutputs Anylevelgreaterthan0meansthattheoutputisclosed
Use “OUTPUT Command-specific fields” tables
to complete the parameter field.
Action number is always
1 for visor control outputs
Operation
Command
Integration ID (example)
#OUTPUT,21,ActionNumber,Parameters
Visor Control Receiver
Learn
Visor Transmitter
Keypad
Outputs
Flash
Full
Security Input
Inputs
1 2
Power
9V
Inputs
C
Full
1 C 2 C
Outputs
3 C
4
C
Flash