Installation Manual

11
Lutron integration protocol
Integrator’s Reference (continued)
HVAC: Command Summary (continued)
HVAC Command-specific fields (continued)
Action NumbersandParameters (continued):
Action Action Number Parameters
Set(#)orGet(?)CallStatus 14
0=None,LastwasHeat
1=HeatStage1
2=HeatStage1and2
3=HeatStage1,2,and3
4=HeatStage3
5=None,LastwasCool
6=CoolStage1
7=CoolStage1and2
8=Off
9=EmergencyHeat
10=Dry
Set(#)orGet(?)CurrentTemperature(°C)
1,4,5
15 Temperature=0 100°C
Set(#)orGet(?)HeatandCoolSetpoints
(°C)
2,3,4
16
SetpointHeat(SPH)=0 100°C
SetpointCool(SPC)=0 100°C
Get(?)HeatandCoolSetpoints(°C)without
EcoOffsetifapplied
2,4
17
SetpointHeat(SPH)=0 100°C
SetpointCool(SPC)=0 100°C
Set(#)orGet(?)SingleSetpoint(°F)andDrifts
3,4
18
SingleSetpoint=
32212°F
NegativeDrift=
015°F
PositiveDrift=
015°F
Set(#)orGet(?)SingleSetpoint(°C)andDrifts
3,4
19
SingleSetpoint=
0100°C
NegativeDrift=
08°C
PositiveDrift=
08°C
NOTES
1  HomeWorksQSsoftwareversion4 1andhigher
2  ChangingthesetpointwillturnEcoModeoffifitiscurrentlyon
3  Toleaveaparameterunchanged,use“255”asthevalueforthatparameterwhenendingthecommand
4  Allowforreportedtemperaturevaluestobezeropadded,withupto3digitsbeforethedecimalpoint,and2digitsafter
–Possiblereportedvaluesof5°C:“005”,“05”,“5”,“005 ”,“005 ”,“5 ”,“005 0”,“05 0”,“5 0”,“005 00”,“05 00”,“5 00”
–Possiblereportedvaluesof5 5°C:“005 5”,“05 5”,“5 5”,“005 50”,“05 50”,“5 50”
–Possiblereportedvaluesof21°C:“021”,“21”,“021 0”,“21 0,“021 00,”“21 00”
–Possiblereportedvaluesof21 5°C:“021 5”,“21 5”,“021 50”,“21 50”
5  SettingofcurrenttemperatureisonlypossibleiftheHVACzoneisconnectedtoa3rdpartyHVACcontroller