Installation Manual
150
Lutron integration protocol
Why Integrate with a QSE-IO?
• KnowthestateoftheContactClosureInputs(CCIs)
• ControlthestateoftheContactClosureOutputs(CCOs)
Integration Capabilities
5ContactClosureInputs(CCIs)and5ContactClosureOutputs TheQSE-IOmodeofoperationisspecied
byitsDIPswitchconguration
• CCIandCCOstatescanbepolledinanyDIPconguration
• CCIeventscanbemonitoredthroughintegrationinanyDIPconguration
• CCIevents(closuresoropeningsofCCIs)canbe‘spoofed’(faked)throughintegrationinDIPcongurations
wheremomentaryCCIsarespecied
• CCOeventscanbemonitoredthroughintegrationinanyDIPconguration
• TheCCOstatelogicistypicallytiedtothestatesoftheCCIsorotherdevicesontheQSlinkandthus,CCO
eventscannotbegeneratedthroughintegrationinmostDIPcongurations;theexceptionsaretheoutput
DIPcongurations(e g ,ShadeOutput,ZoneControlOutput)andtheIntegrationDIPcongurationthat
allowsfullmonitoringofCCIsandcontrolofCCOsthroughintegration
• OccupancyeventscanbemonitoredthroughintegrationwhentheQSE-IOisinanOccupancyDIP
conguration
Supported Command Types
• DEVICEallowsmonitoringofCCIandCCOeventsandpollingofCCI/CCOstatesandincertainQSE-IODIP
congurations,allows‘spoong’ofCCIeventsandgenerationofCCOevents
• OUTPUT(incertainoutput-orientedQSE-IODIPcongurations)allowscontrolandmonitoringoftheCCOs
Compatibility
QS Standalone Quantum RadioRA 2 HomeWorks QS myRoom plus
QSE-IO
Devices (continued)
QSE-IO Control Interface
Model: QSE-IO
CCI
1
CCI 2
CCI 3
CCI 4
COM
CCI 5
V
0-24 V 1 A
0-24 V ½ A
R
O
N
CCO 1 NC
CCO 1 NO
CCO 2 NC
CCO 2 NO
1-2 COM
CCO 3 NC
CCO 4 NO
CCO 3 NO
CCO 4 NC
3-4 COM
CCO 5 NC
5 COM
CCO 5 NO
V
R
MUX
COM
V+
MUX
CCO 1
CCO 2
CCO 3
CCO 4
CCO 5
STAT
QS
800.523.9466
+
1.610.282.3800
www.lutron.com/qs
QSE-IO
24 V 100 mA
243C IND. CONT. EQ.
8 7 6 5 4 3 2 1
4 3 2 1
Continuedonnextpage…