Installation Manual

151
Lutron integration protocol
Devices (continued)
QSE-IO Control Interface (continued)
DEVICECommands
DEVICE Command Formats
DEVICE Command-specific fields
Component Numbers:
Component Component Number Available Actions
CCI1 1 Report(~)closure/opening
1
Poll(?)status
2
Spoof(#)closure/opening
3
CCI2 2 Report(~)closure/opening
1
Poll(?)status
2
Spoof(#)closure/opening
3
CCI3 3 Report(~)closure/opening
1
Poll(?)status
2
Spoof(#)closure/opening
3
CCI4 4 Report(~)closure/opening
1
Poll(?)status
2
Spoof(#)closure/opening
3
CCI5 5 Report(~)closure/opening
1
Poll(?)status
2
Spoof(#)closure/opening
3
CCO1 11 Report(~)closure/opening
4
Poll(?)status
2
Generate(#)closure/opening
3
CCO2 12 Report(~)closure/opening
4
Poll(?)status
2
Generate(#)closure/opening
3
CCO3 13 Report(~)closure/opening
4
Poll(?)status
2
Generate(#)closure/opening
3
CCO4 14 Report(~)closure/opening
4
Poll(?)status
2
Generate(#)closure/opening
3
CCO5 15 Report(~)closure/opening
4
Poll(?)status
2
Generate(#)closure/opening
3
OccupancySensor1 41 Report(~)occupied/unoccupied
3,5
OccupancySensor2 42 Report(~)occupied/unoccupied
3,5
OccupancySensor3 43 Report(~)occupied/unoccupied
3,5
OccupancySensor4 44 Report(~)occupied/unoccupied
3,5
OccupancySensor5 45 Report(~)occupied/unoccupied
3,5
NOTES
1  Monitoringtype2mustbeenabled(seeQSE-CI-NWK-E#MONITORINGsection)
2  NotavailableinQuantum
3  FeaturesupportedinonlysomeQSE-IODIPcongurations
4  Monitoringtype5mustbeenabled(seeQSE-CI-NWK-E#MONITORINGsection)
5  Monitoringtype6mustbeenabled(seeQSE-CI-NWK-E#MONITORINGsection)
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE,5,ComponentNumber,ActionNumber,Parameters
CCI
1
CCI 2
CCI 3
CCI 4
COM
CCI 5
V
0-24 V 1 A
0-24 V ½ A
R
O
N
CCO 1 NC
CCO 1 NO
CCO 2 NC
CCO 2 NO
1-2 COM
CCO 3 NC
CCO 4 NO
CCO 3 NO
CCO 4 NC
3-4 COM
CCO 5 NC
5 COM
CCO 5 NO
V
R
MUX
COM
V+
MUX
CCO 1
CCO 2
CCO 3
CCO 4
CCO 5
STAT
QS
800.523.9466
+
1.610.282.3800
www.lutron.com/qs
QSE-IO
24 V 100 mA
®
243C IND. CONT. EQ.
8 7 6 5 4 3 2 1
4 3 2 1
Continuedonnextpage…