Installation Manual
155
Lutron integration protocol
Devices (continued)
QS Sensor Module (QSM) (continued)
DEVICECommands
DEVICE Command Formats
DEVICE Command-specific fields
Component Numbers:
Component Component Number Available Actions
WiredOccupancysensors 1 – 4 Occupied,Unoccupied
WirelessOccupancysensors1–10 5–14 Occupied,Unoccupied
Pico1Buttons
1,2
61–65 Press,Release
Pico2Buttons
1,2
82–86 Press,Release
Pico3Buttons
1,2
103–107 Press,Release
Pico4Buttons
1,2
124–128 Press,Release
Pico5Buttons
1,2
145–149 Press,Release
Pico6Buttons
1,2
166–170 Press,Release
Pico7Buttons
1,2
187–191 Press,Release
Pico8Buttons
1,2
208–212 Press,Release
Pico9Buttons
1,2
229–233 Press,Release
Pico10Buttons
1,2
250–254 Press,Release
NOTES
1 AllmodelsexceptPJ2-4B:Picobuttonorder(Top,Favorite,Bottom,Raise,Lower)dictatesComponentNumber(see
Pico1example,below):
Pico 1 Button Sample Component Number
Top 61
Favorite 62
Bottom 63
Raise 64
Lower 65
2 ModelPJ2-4B*only:Picobuttonorderis1,2,3,4andcomponentmappingwillbeasbelow:
Pico 1 Button Sample Component Number
1 61
2 64
3 65
4 63
*ModelPJ2-4BissupportedonlyonQSMsoftwareversion7 28andhigher
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE,19,ComponentNumber,ActionNumber,Parameters
Continuedonnextpage…